So how exactly does a monoflange work?

Monoflanges combine the event as high as three valves in a particularly compact body, because of an accurate network of internal passages and valve chambers. But what really happens inside a monoflange valve, once installed?
In a chemical process a higher response speed is necessary for some control applications. Among the variables that affect the response time may be the volume and the distance between process and instruments. If the medium to be measured is gas, and the process tends to fluctuate strongly at times or if the control is crucial, mounting the instrument close to the process is the solution.
Vibrations are also critical, for example, in case that impulse lines are connected to a vessel. The longer the hook-up, the wider may be the amplitude of the vibration causing possible failures of the nozzle. No Good includes one, several needle valves in the compact, flange-shaped body, allowing a substantial reduction in volume, dimensions, weight and potential leakage points.
Monoflange is the solution
Depending on requirements of the plant it really is installed in, the monoflange can incorporate one, several valves. In a monoflange with two valves (block & bleed), one valve (with a blue cap) isolates the procedure and another (with a red cap) regulates the venting of the medium trapped in the instrument. This is mostly found in applications that are relatively uncritical (e.g. low pressure) or in which a first shut-off valve is provided just before the monoflange.
The safest configuration, and the main one we advise for aggressive media or critical operating conditions, may be the three-valve monoflange or the so-called double block & bleed (DBB), which features two shut-off valves in series and one valve for venting.
Monoflange functionality
The monoflange bodies are drilled internally with holes which connect the annular valve chambers.
The next picture illustrates the procedure within a DBB monoflange:
The flow enters the monoflange from the pipeline and stops below the initial shut-off valve [1];
When the first shut-off valve [1] opens, the flow proceeds towards the next shut-off valve [2] ; when the valve [2] is open, the instrument is thus linked to the process line;
Once the first shut-off valve [1] is closed, the medium trapped between valve and instrument can be discharged via the vent valve [3] through the vent outlet. Both shut-off valves [1, 2] come in an angled position, that allows the flow to feed them.
Both shut-off valves allow a better isolation from the procedure: In case the first shut-off valve will not isolate the medium properly, the second one will become a safety means against accidental leaks. In some cases, customer specifications do not allow the medium to be in touch with the instrument when it is not measuring. That is why the medium shall be discharged utilizing the vent line. In other cases ? as a result of vent line ? instruments could be easily calibrated without dismounting them from the line.